HomeMy WebLinkAbout1975-11-26 - Resolution No. 75-21RESOLUTION NO. 75-21
E
RESOLUTION OF THE BOARD OF DIRECTORS OF YORBA LINDA COUNTY
WATER DISTRICT AMENDING THE RULES 9 REGULATIONS REGARDING
CROSS-CONNECTIONS
WHEREAS, it has come to the attention of the Board of Directors of
the Yorba Linda County Water District that a comprehensive outline
to prevent cross-connection and backflow should be adopted,
NOW, THEREFORE BE IT RESOLVED BY THE BOARD OF DIRECTORS OF THE
Yorba Linda County Water District that Section "5.2 Protecting
Cross-Connection" of the Rules and Regulations of the Yorba Linda
County Water District with Regard to the Rendition of Water Service
be revised and amended as follows:
SECTION 5.2.1 PURPOSE:
The purpose of this resolution is to protect the District water
supply against actual or potential cross-connection by isolating
within the premises contamination or pollution that may occur
because of a cross-connection on the premises and comply with the
Regulations of the State Department of Public Health contained in
Title 17 of the California Administrative Code under,"Regulations
Relating to Cross-Connection". It is the intent of this resolution
to recognize that there are varying degrees of hazard and to apply
the principle that the degree of protection should be commensurate
with the degree of hazard.
SECTION 5.2.2 DEFINITIONS:
A. Approved Air-Gap Separation. The term "approved air=gap separation"
means a physical break between a supply pipe and a receiving vessel
and approved by the District. The physical break shall be at least
double the diameter of the supply pipe, measured vertically above the
top rim of the vessel, and shall in all cases be at least one inch.
B. Approved Backflow Device. The term "approved backflow device"
means a device tested and approved by the Foundation for Cross-
connection Control and Hydraulic Research at the University of
Southern California and acceptable to the District. To be approved,
a device must be readily accessible for maintenance and testing. The
term "approved backflow device" includes approved double check valve
assembly, approved reduced pressure principle backflow protection
ci vice, and approved air-gap separation.
C. Approved Double Check Valve Assembly. The term "approved double
check valve assembly means an approvF_,d backflow device consisting
of at least two independently acting check valves including tightly
closed shut-off valves on each side of the check valve assembly and
suitable leak detector drains plus connections available for testing
-the water tightness of each valve.
D. Approved Reduced Pressure Principle Backflow Prevention Device.
The term approved reduced pressure principle backflow prevention
device" means an approved backflow device which incorporates two
or more check valves and an automatically operating differential
relief valve located between the two checks, two shut-off valves,
and equipped with necessary appurtenances for testing.
E.Approved Water Supply. The term "approved water supply" means any
water supply approved by or under the supervision of a public health
agency of the State of California and acceptable to the District.
-1-
y \ `
F. Auxiliary Water Supply. The term "auxi~j_ary water supply" means
any water on or available to the premises other than the District
after it has passed the service connection.
G. Certified Tester. The term "Certified tester" means a person
who has met the requirements of and has been certified by the
Health Department of the County of Orange as qualified to inspect
and maintain backflow prevention devices. A certified tester must
also be acceptable to the District. The District may maintain and
make available a list of persons qualified to inspect and main-
tain backflow prevention devices. This list is provided as a con-
venience only and should not in any way be considered as an endorse-
ment of the water district.
H. Cross-Qonn,~,ction. The term "cross-connection" means any real or
potent al unprotected connection between any part of the District
water supply and any other source or system containing water or
substance that might cause a health, system or pollution hazard
if it entered the District water supply facilities.
I. Healt azard. The term "health hazard" means an actual or
potential ~hreat of degradation of the District water supply to
a degree or intensity that there is or may be a danger to health.
J. Pollution Hazard. The term "pollution hazard" means an actual
or potential threat to the potability of the public water supply
or of physical damage to the District's water supply facilities
which would not constitute a health or system hazard.
K. Servi~ge Connection. The term "service connection" means the
point where the consumer system meets the District's water supply
facilities.
L. System Hazard. The term "system Hazard" means an actual or
potential threat of physical damage to the District's water supply
facilities which would have a protracted effect on the quality of
water in the system.
SECTION 5.2.3 WHERE PROTECTION IS REQUIRED.
A. Cross-Connections. Each service connection to premises where a
cross-connection may exist shall be protected by an approved back-
flow device unless the auxiliary water supply is accepted as an
approved water supply.
B. Internal Abatement. An approved backflow device need not be
installed on service connections where cross-connections are
abated to the satisfaction of the water district.
C. Consumer Duty. The responsibility to provide, test and maintain
protective devices as required by this Article rests with the water
user.
SECTION 5.2.4 TYPE OF PROTECTION:
A. Criteria The type of approved backflow device shall depend
upon the degree of hazard. The decision as to which device shall be
used rests in the discretion of the District and shall depend upon
the facts of each particular situation. In determining the degree
of hazard and the type of approved backflow device required, the
following criteria shall be used:
1. Health or System Hazard. An approved air-gap
separation or an approved reduced pressure principle back-flow
prevention device shall be used where there is an existing or
potential health or system hazard. In cases where the existing
or potential health or system hazard is determined by the District
to be very remote, the District may allow other protection.
2. Pollution Hazard. A double check valve assembly may
be used where there is an existing or potential pollution hazard.
B. Guidelines. The following guidelines are established to im-
plement the proceeding criteria:
1. Stri4ctu,reS of Three or More Stories. At the
service connection to premises where there are structures of three
stories or more in height, the District water supply shall be pro-
tected by an approved backflow device.
2. RecirG'4~lating Water. At the service connection to
premises containing recirculating water systems (hot or cold),
the District water supply shall be protected by an approved back-
flow device.
3. Five or More Units. At the service connection to any
premises where there are multiple dwellings with five or more
individual units being served through one metering system, the
District water supply shall be protected by an approved backflow
device.
4. Health or System Hazard From Auxiliary Water Supply.
At the service connection to any premises where there is an aux-
iliary water supply which may constitute a health or system hazard,
an approved air-gap separation or an approved reduced pressure back-
flow prevention device shall be installed.
5. Sewer~ae Treatment, etc. Fac~_ ties. At the service
connection to any sewerage treatment plant, sewerage pumping station,
or storm water pumping station, the District water supply shall be
protected by an approved air-gap separation. The air-gap separation
shall be located as close as practicable to the meter and all piping
between the meter and the receiving tank shall be entirely visible.
If, in the opinion of the District, an air-gap separation provides
insufficient protection, the District may require installation of
additional approved backflow devices or devices.
6. Ho pitals., Mortuaries, etc. At the service conn-
ection to hospitals, medical buildings, mortuaries, and other
premises where special hazards exist, the District water supply
shall be protected by an approved reduced pressure principle back-
flow prevention device.
7. Commercial or Industrial Buildings. At the service
connection to premises containing commercial or industrial buildings
subject to varying and unknown use because of changes in tenancy, the
District water supply shall be protected by an approved backflow
device.
SECTION 5.2.5 INSPECTIQN OF BACKFLOW DEVICES:
A. Annual Inspection by Certified Tf;,sti r. Backflow devices shall be
inspected and certified operational at least once a year. All in-
spections shall be conducted by a certified tester who shall prepare
a report and certificate of operational readiness.
B. Water Uses Duty. The water user shall cause annual inspections
to be made at the expense of the water user. Defective devices shall
-3-
be repaired, overhauled or replaced at the expense of the water user.
C. Reports. Reports of inspection and corrective measures shall be
submitted to the District within ten days of the inspection by the
certified tester along with his certificate of operational read-
iness.
D. More Frequent Inspection. Where successive annual reports
indicate defective operation of a backflow device, the District
may require more frequent inspection.
E. Duty of Tester. The certified tester shall be responsible for
the competency of inspections, corrective actions, and the accuracy
of reports required under this section.
F. District Inspection and Location of Backflow Device-It is the
consumer responsibility to have the necessary backflow device in-
stalled in a location which is readily available for periodic
inspection.
Upon 24 hour notice the District may at its option perform periodic
inspection of a consumers backflow device.
SECTION 5.2.6 REGULATIONS
When it becomes necessary, on account of low pressure or special
operating conditions, to install a booster pump on the service to
any premises, such pump shall be equipped with a low pressure cut-
off switch designed to shut-off the pump when the pressure on the
inlet side is 25 p.s.i.g. or lower. It shall be the duty of the
consumer to maintain the cut-off device in proper working order, and
to certify to the District at least once a year that the device is
operable. Low pressure cut-off device certification shall be by a
person deemed competent by the District.
SECTION 5.2.7 ENFORCEMENT :
A. New Service Connections. No new service connections shall be
completed until the provisions of this resolution have been complied
with to the satisfaction of the District.
B. Termination of Water Service. The District may immediately dis-
continue service to any premises where a cross-connection or other
hazard to the District's water supply is found to exist. Any user who
violates any of the provisions of this article or alters, bypasses,
or renders inoperat-imf~ any backflow >revent:iLon devz-e installed
under the provisions of this chapter shall be subject to immediate
termination of water service.
Passed and Adopted this 26th day of November 1975 by the
following called vote:
Ayes: Clodt, Wagner, Lindow and Korn
Noes: None
Absent: Knauft
Abstaining: None
ATTEST:
Secreta
l
OF BOOSTER PUMPS:
President
-4-